1. According to DIN 18014, when does one need a ring earth electrode and when a foundation earth electrode?
Foundation earth electrode:
For all new buildings because a foundation earth electrode is required according to DIN 18015, the current technical connection conditions of the power supplier and the future connection rules AR4100.
Ring earth electrode:
When the earth electrode in the foundations (foundation earth electrode) does not have sufficient contact with the earth. As a rule this applies to building waterproofing, i.e. foundations with increased earth contact resistance like, e.g. a white tank, perimeter insulation, foam glass gravel
2. Why do the connection points on the ring earth electrode have to be wrapped in insulating tape if V4A material is used?
Connection points in the soil are generally a weak point - in terms of corrosion and when high quality material like V4A is used. This is why the standard (DIN 18014) says that these should be wrapped in insulating tape.
3. What is the right mesh size for ring and foundation earth electrodes?
The maximum mesh size for both foundation earth electrodes and ring earth electrodes is 20 m x 20 m.
However, in combination with a lightning protection system the mesh size for the ring earth electrode must be 10 m x 10 m. To keep your options open with regard to retrofitting a lightning protection system, it is advisable to opt for a mesh size of 10 x 10 m with ring earth electrodes.
4. Does one always need a ring earth electrode with a lighntning protection system?
No. According to DIN 18014, the earthing system required for a lightning protection system can consist of either a ring earth electrode or a foundation earth electrode. The lightning protection system must then be erected according to Part 3 for the EN 62305 lightning protection standard.
5. What are the distances from the ring earth electrode and foundation earth electrode to the edge of the building?
The gap required between the ring earth electrode and the building is at least 1 metre and it should be buried at least 0.8 m deep. The foundation earth electrode should be installed as a closed ring in the floor slab at the outside edge of the foundations sheathed in at least 5 cm of concrete.
6. What about buildings with individual foundations?
Individual foundations require an earth electrode of at least 2.5 m in length. The individual foundations must be interconnected using corrosion-resistant earthing materials V4A - preferably in direct contact with the earth. If waterproof concete is used in the individual foundations, a ring earth electrode must be fitted.
7. Is it always necessary to mount earth rods?
No earth rods are required for the standard configuation of the foundation or ring earth electrode. Earth rods should be used as an alternative measure if it is not possible to install an earthing system which conforms with DIN 18014.
In this case, earth rods with a length of at least 3 m can be installed round the building as an additional measure to the ring earth electrode. The best position for these is the corners of the building. The distance between the earth rods may not exceed 20 m if there is no lightning protection system and 10 m with a lightning protection system. The earth rods must be connected to the ring earth electrode.
8. Why does one need a functional bonding conductor and a ring earth electrode?
According to DIN 18014, a functional bonding conductor is required in the concrete foundations in addition to a ring earth electrode because it is here that the internal equipotential bonding of the building structure (reinforcements, metal constructions, etc.) is established. The functional bonding conducter should be connected to the reinforcements every 2 m and to the ring earth electrode every 20 m (if lighnting protection is required, every 10 m).
9. The customer has a mixture, e.g. white tank + individual foundations + floor slab (for example, a warehouse with part concrete floor slab and part paving).
How can one comply with the standard here?